Delta DVP-ES2 — 5.5 Types of Sequences

5. Sequential Function Chart Combination example 2: (Includes alternative divergence/convergence and simultaneous divergence/convergence) Step Ladder Diagram: SFC Diagram: M1002 S0 X0 S30 Y0 X1 X1 S31 Y1 S32 Y2 X2 X3 X4 S33 Y3 X5 S34 Y4 X6 S36 Y6 S35 Y5 S37 Y7 X7 S0 Restrictions on Divergence Sequence: 1. Max. 8 step points could be used for single divergence sequence. As the diagram below, there 2. Max. 16 step points could be used for the convergence of multiple diverted sequences. As the are maximum 8 diverged steps S30 ~ S37 after step S20. diagram below, there are 4 steps diverged after S40, 7 steps diverged after S41, and 5 steps diverged after S42.

There are maximum 16 loops in this sequence. 3. Users can assign a step in the sequence to jump to any step in another sequence. 5-21 M1002 ZRST S0 S127 SET S0 S0 X0 S SET S30 S30 S Y0 X1 SET S31 X1 SET S32 S31 S Y1 X2 SET S33 S32 S Y2 X3 SET S33 S33 S Y3 X4 SET S34 SET S36 S34 S Y4 X5 SET S35 S35 S Y5 S36 S Y6 X6 SET S37 S37 S Y7 S35 S37 X7 S S S0 RET END ZRST S0 S127 SET S0 SET S30 RET END SET S31 SET S32 SET S33 SET S33 SET S34 SET S36 SET S35 SET S37