DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 7.3.2 The CANopen Communication Object The CANopen communication protocol contains the following communication objects. PDO (process data object) The PDO provides the direct visit channel for the device application object, is used to transmit the real-time data, and has high priority. Every byte in the PDO CAN message data list is used to transmit the data. The rate of making use of the message is high. There are two kinds of uses for PDOs. The first is data transmission and the second data reception. They are distinguished by Transmit-PDOs (TxPDOs) and Receive-PDOs (RxPDOs).
Devices supporting TxPDOs are PDO producers, and devices which are able to receive PDOs are called PDO consumers. The PDO is described by means of the “producer/consumer mode”. The data is transmitted from one producer to one or many consumers. The data which can be transmitted are limited to 1-byte data to 8-byte data. After the data is transmitted by the producer, the consumer does not need to reply to the data. Every node in the network will detect the data information transmitted by the transmission node, and decides whether to process the data which is received. Every PDO is described by two objects in the object dictionary:
The PDO communication parameters and the PDO mapping parameters The PDO communication parameters: The COB-ID which will be used by PDO, the transmission type, the prohibition time, and the cycle of the counter The PDO mapping parameters: They include the object list in an object dictionary. These objects are mapped into the PDO, including the data length (in bits). To explain the contents of the PDO, the producer and the consumer have to understand the mapping. The PDO transmission mode: synchronous and asynchronous Synchronous: Synchronous periodic and synchronous non-periodic Asynchronous: The PDO is transmitted when the data changes, or it is transmitted after a trigger.
The transmission modes supported by are as follows. Mode 0: The PDO information is transmitted only when the PDO data changes and the synchronous signal comes. Modes 1~240: One piece of PDO information is transmitted every 1~240 synchronous signals. Mode 254: The trigger is defined the manufacturer. The definition of the PLC is the same as mode 255. Mode 255: PDO is transmitted when the data changes, or it is transmitted after a trigger. 7-10 Type PDO transmission Periodic Non-periodic Synchronous Asynchronous RTR 0 X X 1 – 240 X X 254 X 255 X