2. Programming Concepts I000/I001(X0), I100/I101(X1), I200/I201(X2), I300/I301(X3), I400/I401(X4), I500/I501(X5), I600/I601(X6), I700/I701(X7). When IRET instruction is executed, program execution returns to the address before interrupt occurs. When X0 (C243) works with I100/I101 (X1), X0/X1 (C246, C248, C252) works with I400/I401, the value of C243, C246, C248, C252 will be stored in (D1240, D1241) When X2 (C244) works with I300/I301 (X3), X2/X3 (C250, C254) works with I500/I501, the value of C244, C250, C254 will be stored in (D1242, D1243). 2.
Timer interrupt PLC automatically interrupts the currently executed program every a fixed period of time (2ms~99ms or 0.5ms~9.9ms) and jumps to the execution of a designated interruption subroutine 3. Counter interrupt The high-speed counter comparison instruction API 53 DHSCS can designate that when the comparison reaches the target, the currently executed program will be interrupted and jump to the designated interruption subrountine executing the interruption pointers I010, I020, I030, I040, I050 ,I060, I070, I080. 4. Communication interrupt I140: Communication instruction RS (COM1 RS-232) can be designated to send interrupt request when specific charcters are received.
Interrupt I140 and specific characters is set to low byte of D1167. This function can be adopted when the PLC receives data of different length during the communication. Set up the specific end word in D1167 and write the interruption subroutine I140. When PLC receives the end word, the program will execute I140. I150: Communication instruction RS (COM2 RS-485) can be designated to send interrupt request when specific charcters are received. Interrupt I150 and specific characters is set to low byte of D1168. This function can be adopted when the PLC receives data of different length during the communication. Set up the specific end word in D1168 and write the interruption subroutine I150.
When PLC receives the end word, the program will execute I150.. I160: Communication instruction RS (COM3 RS-485) can be designated to send interrupt request when specific charcters are received. Interrupt I160 and specific characters is set to low byte of D1169 This function can be adopted when the PLC receives data of different length during the communication. Set up the specific end word in D1169 and write the interruption subroutine I160. When PLC receives the end word, the program will execute I160 2.16 Applications of Special M Relays and D Registers Function Group PLC Operation Flag Number M1000~M1003 Contents: These relays provide information of PLC operation in RUN status. M1000:
NO contact for monitoring PLC status. M1000 remains “ON” when PLC is running. M1000 Y0 PLC is running Keeps being ON Normally ON contact in PLC RUN status M1001: NC contact for monitoring PLC status. M1001 remains “OFF” when PLC is running. M1002: Enables single positive pulse for the first scan when PLC RUN is activated. Used to initialize registers, ouptuts, or counters when RUN is executed.. M1003: Enables single negative pulse for the first scan when PLC RUN is activated. Used to initialize 2-45