Delta DVP-ES2 — 2.16 Applications of Special M Relays and D Registers

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 2. If set value for RTC is invalid. RTC will display the time as Second→0, Minute→0, Hour→0, Day→1, Month→1, Week→1, Year→0. 3. Only when power is on can RTCs of SS2 series perform the fuction of timing. Memory of RTC is latched. RTC will resume the time when power is down. For higher accuracy of RTC, please conduction calibratoin on RTC when power resumes. 4. RTCs of SA2/SE V1.0 and ES2/EX2/SX2 V2.0 series can still operate for one or two weeks after the power is off (they vary with the ambient temperature). Therefore, if the machine has not operated since one or two weeks ago, please reset RTC. 5. Methods of modifying RTC:

a) Apply TWR instruction to modify the built-in real time clock. Please refer to TWR instruction for detail. b) Use peripheral devices or WPLSoft to set the RTC value. Function Group π (PI) Number D1018~D1019 Contents: 1. D1018 and D1019 are combined as 32-bit data register for storing the floating point value ofπ 2. Floating point value = H 40490FDB Function Group Adjustment on Input Terminal Response Time Number D1020, D1021 Contents: 1. D1020 can be used for setting up the response time of receiving pulses at X0 ~X7 for ES2 series MPU. Default: 10ms, 0~20ms adjustable. 2.

D1021 can be used for setting up the response time of receiving pulses at X10~X17 X7 for 28SS2 V3.42 /28SA2 V3.0 /26SE with firmware V2.0 or later versions. Default: 10ms, 0~20ms adjustable. 3. When the power of PLC goes from “OFF” to “ON”, the content of D1020 is set to 10 automatically. Terminal response time X0 0ms 0 1 1ms Set by D1020 (default: 10) X7 10ms 10 Update input status 15 15ms Status memory 4. If the following programs are executed, the response time of X0 ~ X7 will be set to 0ms. However, the fastest response time of input terminals will be 50μs due to that all terminals are connected with RC filters.. M1000 normally ON contact 5.

It is not necessary to adjust response time when using high-speed counters or interrupts 2-48 30~ 59 second: mimute + 1; second reset to 0 D1313 Second 0~59 D1314 Minute 0~59 D1315 Hour 0~23 D1316 Day 1~31 D1317 Month 1~12 D1318 Week 1~7 D1319 Year 0 ~ 99 (last 2 digits of Year in A.D.) MOV K0 D1020