Delta DVP-ES2 — D.1.5 Calculating the maximum current consumed by a system

Appendix D Introducing the Current Consumption of Slim PLCs/Extension Modules D.1.3 Current consumption of a special input/output module (+24VDC) A special input/output module must be supplied with +24VDC power. D.1.4 Current consumption of a left-side high-speed special module (+24VDC) D.1.5 Calculating the maximum current consumed by a system Example: 28SV2 + 16SP + 04AD-S + 04TC-S + EN01-SL The power module optionally purchased is DVPPS02. (It supplies 2A current.) Maximum current consumed: Internal  170 + 65 + 30 + 30 + 60 = 355 (mA) External  3.8A + 5A + 83mA + 83mA = 9A > 2A Not pass Conclusion: The 2A current supplied by DVPPS02 is sufficient for the PLC and the special modules.

If the external I/O terminals are connected to loads, it is suggested that users should purchase an extra power module.

D-3 Model 04AD-S 06AD-S 04DA-S 06XA-S 04PT-S 04TC-S 01PU-S Item Internal maximum current 30 30 30 30 30 30 30 consumed by the IO-BUS (mA) Maximum current 83 83 167 83 83 83 105 consumed by the external AIO (mA) Model Item EN01-SL COPM-SL DNET-SL 04AD-SL 04DA-SL 02LC-SL 01LC-SL Internal maximum current consumed by the IO-BUS (mA) 60 50 50 40 40 40 40 Maximum current consumed by the external AIO (mA) 0 0 0 15 80 125 125 Model Internal current consumption External current consumption DVP28SV11T2 170mA 3.8A DVP16SP11R 65mA 5A DVP04AD-S 30mA 83mA DVP04TC-S 30mA 83mA DVPEN01-SL 60mA 0