DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming F.1 General Specifications F-2 Item Specifications Operating temperature 0 to 55°C Storage temperature -25 to 70°C 5–95% No condensation Operating humidity 5–95% No condensation Storage humidity Work environment No corrosive gas exists. Installation location In a control box Pollution degree 2 Ingress protection IP20 (IP ratings) Surge voltage withstand 1,500 VAC (Primary-secondary), 1,500 VAC (Primary-PE), 500 VAC (Secondary-PE) level Above 5MΩ The voltage between all inputs/outputs and the ground is 500 VDC. Insulation voltage ESD: 8KV Air Discharge EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O:
250V Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m Noise Immunity The diameter of the ground should not be less than the diameters of the cables connected to the terminals L and N. It is required to use grounding if more than one PLC is being used at the same time. Ground Vibration / Shock International Standard IEC61131-2, IEC 68-2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27 (TEST Ea) resistance Ambient air Operating: 1080 ~ 795hPa (-1000 ~ 2000 m) Storage:1080 ~ 660hPa (-1000 ~ 3500m) temperature-barometric pressure-altitude