Delta DVP-ES2 — 2.16 Applications of Special M Relays and D Registers

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming The description of D1115 for 30EX2: The analog input modes for 30EX2: The analog output modes for 30EX2: The example of setting D1115 for 30EX2: If the analog input mode of AD0 is the two-wire NI100, the analog input mode of AD1 is the three-wire 1000, the analog input mode of AD2 is the voltage mode (+1 V~ +5 V), and the analog output mode of DA0 is the current mode (+4 mA ~ +20 mA), the setting value in D1115 is H’2A61. Function Group Enable 2-speed output function of DDRVI/DDRVA instruction Number M1119 Contents: When M1119 is ON, 2-speed output function of DDRVI/DDRVA will be enabled. Example:

Assume that D0 (D1) is the first speed and D2(D3) is the second speed. D10(D11) is the output pulse number of the first speed and D12(D13) is the output pulse number of the second speed. 2-56 Bit15~12 Bit11~8 Bit7~4 Bit3~0 Analog output mode of DA0 Analog input mode of AD2 Analog input mode of AD1 Analog input mode of AD0 Code 0x0 0x1 0x2 0x3 Description Two-wire PT100 Three-wire NI100 Two-wire PT1000 Two-wire NI1000 Code 0x4 0x5 0x6 0x7 Description Three-wire PT100 Three-wire NI100 Three-wire PT1000 Three-wire NI1000 Code 0x8 0x9 0xA 0xB Description Voltage: -10 V~+10 V Voltage: -5 V~+5 V Voltage: +1 V~+5 V Current: -20 mA~+20 mA Code 0xC 0xD 0xE 0xF Description Current:

+4 mA~+20 mA Reserved Unused Code 0x0 0x1 0x2 0xF Description Voltage: -10 V~+10 V Current: +0 mA~+20 mA Current: +4 mA~+20 mA Unused