DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Function Group Program Execution Error Number M1067~M1068, D1067~D1068 Contents: Error code explanation: Function Group I/O Modules Detection Number D1140, D1142, D1143, D1145 Contents: D1140: Number of right-side modules (AIO, PT, TC, etc.), max. 8 modules can be connected. D1142: Number of input points (X) on DIO modules. D1143: Number of output points (Y) on DIO modules. D1145: Number of left-side modules (AIO, PT, TC, etc.), max. 8 modules can be connected. (Only applicable for SA2/SX2/SE). Function Group Reverse Interrupt Trigger Pulse Direction Number M1280, M1284, M1286 Contents: 1.
The falgs should be used with EI instruction and should be inserted before EI instruction 2. The default setting of interrupt I101 (X0) is rising-edge triggered. If M1280 is ON and EI instruction is executed, PLC will reverse the trigger direction as falling-edge triggered. The trigger pulse direction of X1 will be set as rising-edge again by resetting M1280. 3. When M0 = OFF, M1280 = OFF. X0 external interrupt will be triggered by rising-edge pulse. 4. When M0 = ON, M1280 = ON. X0 external interrupt will be triggered by falling-edge pulse. Users do not have to change I101 to I000.
M0 EI FEND I001 M1000 IRET Function Group Stores Value of High-speed Counter when Interrupt Occurs Number D1240~D1243 Contents: 1. If extertal interrupts are applied on input points for Reset, the interrupt instructions have the priority in using the input points. In addition, PLC will move the current data in the counters to the associated data registers below then reset the counters.
END 2-58 Device Explanation Latched STOP→RUN RUN→STOP M1067 Program execution error None Clear Unchanged M1068 Execution error locked None Unchanged Unchanged D1067 Error code for program execution None Clear Unchanged D1068 Address of program execution error None Unchanged Unchanged D1067 error code Function 0E18 BCD conversion error 0E19 Divisor is 0 0E1A Use of device exceeds the range (including E, F index register modification) 0E1B Square root value is negative 0E1C FROM/TO instruction communication error OUT M1280 INC D0