2. Programming Concepts 2. Special D and special M corresponding to Slave ID1~ Slave ID8: (M1353 = OFF, access available for only 16 words) ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↓ 3. Special D and special M corresponding to Slave ID9~ Slave ID16:
(M1353 = OFF, access available for only 16 words) ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↓ 2-61 MASTER PLC SLAVE ID 1 SLAVE ID 2 SLAVE ID 3 SLAVE ID 4 SLAVE ID 5 SLAVE ID 6 SLAVE ID 7 SLAVE ID 8 Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Special D registers for storing the read/written 16 data (Auto-assigned) D1480 │ D1495 D1496 │ D1511 D1512 │ D1527 D1528 │ D1543 D1544 │ D1559 D1560 │ D1575 D1576 │ D1591 D1592 │ D1607 D1608 │ D1623 D1624 │ D1639 D1640 │ D1655 D1656 │ D1671 D1672 │ D1687 D1688 │ D1703 D1704 │ D1719 D1720 │ D1735 Data length for accessing the Slave (Max 16 pieces of data, no access is performed when SV = 0) D1434 D1450 D1435 D1451 D1436 D1452 D1437 D1453 D1438 D1454 D1439 D1455 D1440 D1456 D1441 D1457 Starting reference of the Slave to be accessed* D1355 D1415 D1356 D1416 D1357 D1417 D1358 D1418 D1359 D1419 D1360 D1420 D1361 D1421 D1362 D1422 M1355 = ON, Slave status is user-defined.
Set the linking status of Slave manually by M1360~M1367. M1355 = OFF, Slave status is auto-detected. Linking status of Slave can be monitored by M1360~M1367 M1360 M1361 M1362 M1363 M1364 M1365 M1366 M1367 Data interchange status of Slaves.
M1376 M1377 M1378 M1379 M1380 M1381 M1382 M1383 Error flag for errors occurred when reading and writing (ON = normal; OFF = error) M1392 M1393 M1394 M1395 M1396 M1397 M1398 M1399 “Reading completed” flag (turns “Off” whenever access of a Slave is completed) M1408 M1409 M1410 M1411 M1412 M1413 M1414 M1415 “Writing completed” flag (turns “Off” whenever access of a Slave is completed) M1424 M1425 M1426 M1427 M1428 M1429 M1430 M1431 Slave PLC* SLAVE ID 1 SLAVE ID 2 SLAVE ID 3 SLAVE ID 4 SLAVE ID 5 SLAVE ID 6 SLAVE ID 7 SLAVE ID 8 Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in Read out Write in D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 MASTER PLC SLAVE ID 9 SLAVE ID 10 SLAVE ID 11 SLAVE ID 12 SLAVE ID 13 SLAVE ID 14 SLAVE ID 15 SLAVE ID 16 Read out Write in Read out Write in Read out Write in Reado ut Write in Read out Write in Read out Write in Read out Write in Read out Write in Special D registers for storing the read/written 16 pieces of data (Auto-assigned) D1736 │ D1751 D1752 │ D1767 D1768 │ D1783 D1784 │ D1799 D1800 │ D1815 D1816 │ D1831 D1832 │ D1847 D1848 │ D1863 D1864 │ D1879 D1880 │ D1895 D1896 │ D1911 D1912 │ D1927 D1928 │ D1943 D1944 │ D1959 D1960 │ D1975 D1976 │ D1991 Data length for accessing the Slave (Max 16 pieces of data, no access is performed when SV = 0) D1442 D1458 D1443 D1459 D1444 D1460 D1445 D1461 D1446 D1462 D1447 D1463 D1448 D1464 D1449 D1465 Starting reference of the Slave to be accessed* D1363 D1423 D1364 D1424 D1365 D1425 D1366 D1426 D1367 D1427 D1368 D1428 D1369 D1429 D1370 D1430 M1355 = ON, Slave status is user-defined.
Set the linking status of Slave manually by M1368~M1375. M1355 = OFF, Slave status is auto-detected.
Linking status of Slave can be monitored by M1368~M1375 M1368 M1369 M1370 M1371 M1372 M1373 M1374 M1375 Data interchange status of Slaves M1384 M1385 M1386 M1387 M1388 M1389 M1390 M1391 Access error flag (ON = normal; OFF = error) M1400 M1401 M1402 M1403 M1404 M1405 M1406 M1407 “Reading completed” flag (turns “Off” whenever access of a Slave is completed) M1416 M1417 M1418 M1419 M1420 M1421 M1422 M1423 “Writing completed” flag (turns “Off” whenever access of a Slave is completed) M1432 M1433 M1434 M1435 M1436 M1437 M1438 M1439 Slave PLC* SLAVE ID 9 SLAVE ID 10 SLAVE ID 11 SLAVE ID 12 SLAVE ID 13 SLAVE ID 14 SLAVE ID 15 SLAVE ID 16 Read out Write in Read out Write in Read out Write in Reado ut Write in Read out Write in Read out Write in Read out Write in Read out Write in D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215 D100 │ D115 D200 │ D215