DVP-ES3 Series Operation Manual *3. If noise in the input voltage results in noise interference in the wiring, connect the module to a capacitor with a capacitance between 0.1–0.47 μF with a working voltage of 25 V. *4. Connect FE of the shielded cable to ground. *5. Connect the terminal to ground. *6. Every channel can work with the wiring shown above. 4.8.2 Wiring DVP02DA-E2/DVP04DA-E2 Voltage output CHX -10V~+10V *4 CH1 VO1 _4 Shielded cable*1 AG IO1 AC motor drive, recorder, proportioning valve FE AG *4 Current output CHX 0mA~20mA CH4 AG *3 24VDC DC/DC +15V 24V Converter -15V AG *1. Use shielded cables to isolate the analog input signal cable from other power cables. *2.
If noise in the input voltage results in noise interference in the wiring, connect the module to a capacitor with a capacitance between 0.1–0.47 μF with a working voltage of 25 V. *3. Connect the terminal to ground. *4. Every channel can work with the wiring shown above. 4-36 *2 VO4 IO4 AG FE AC motor drive, recorder, proportioning valve Shielded cable*1 FE 0V