Delta DVP-ES3 — 5.3.1 DVP04AD-E2 Control Registers

DVP-ES3 Series Operation Manual  Mode 2:  Mode 3: +32384 +32384 +32000 +32000 Digital output Digital output +16000 +16000 Gain 0 -384 -384 5V 2.5V Offset Voltage input Offset Voltage input _5  Mode 4: 5-22 Mode 2 of CR#2 ~ CR#5 0V ~ +10V, Default: Gain = 16,000(= ),Offset = 0 Mode 3 of CR#2 ~ CR#5 0V ~ +5V, Default: Gain = 16,000(= ),Offset = 0 R ange of digital conversion 0 ~ +32,000 c Max./Min. range of digital -384 ~ +32,384 onversion 0 0 4 Gain 5V 10 Mode 4 of CR#2 ~ CR#5 -20mA ~ +20mA, Default: Gain = 16,000(= ), Offset = 0 Mode 4 of CR#2 ~ CR#5 R ange of digital conversion -32,000 ~ +32,000 c Max./Min.

range of digital -32,384 ~ +32,384 onversion +32384 +32000 Digital output +16000 -20mA 0 10mA 10mA 20mA Offset Gain -16000 Current input -32000 -32384 Mode 5 of CR#2 ~ CR#5 0mA ~ +20mA, Default: Gain = 16,000(= ), Offset = 0 Mode 6 of CR#2 ~ CR#5 +4mA ~ +20mA, Default: Gain = 19,200 (= ), Offset = 6,400(= ) R ange of digital conversion 0 ~ +32,000 c Max./Min. range of digital -384 ~ +32,384 onversion