Delta Electronics DVP-ES3 — 5.3.2 DVP02DA-E2 / DVP4DA-E2 Control Registers

DVP-ES3 Series Operation Manual 5.3.2 DVP02DA-E2 / DVP4DA-E2 Control Registers _5 5-24 CR# Attrib. Register name Explanation 0 O R Model name Set up by the system, model code: DVP02DA-E2 = H’0041; DVP04DA-E2 = H’0081 1 O R Firmware version Display the current firmware version in hex. 2 O R/W CH1 output mode setting Output mode: Default = H’0000. Mode 0 (H’0000): Voltage output (±10V) Mode 1 (H’0001): Current output (0~+20mA) Mode 2 (H’0002): Current output (+4~+20mA) Mode -1 (H’FFFF): All channels are unavailable 3 O R/W CH2 output mode setting 4 O R/W CH3 output mode setting 5 O R/W CH4 output mode setting 16 X R/W CH1 output signal value Voltage output range: K-32,000~K32,000.

Current output range: K0~K32,000. Default: K0. CR#18~CR#19 of DVP02DA-E2 are reserved. 17 X R/W CH2 output signal value 18 X R/W CH3 output signal value 19 X R/W CH4 output signal value 28 O R/W Adjusted Offset value of CH1 Set the adjusted Offset value of CH1 ~ CH4. Default = K0 29 O R/W Adjusted Offset value of CH2 30 O R/W Adjusted Offset value of CH3 31 O R/W Adjusted Offset value of CH4 34 O R/W Adjusted Gain value of CH1 Set the adjusted Gain value of CH1 ~ CH4. Default = K16,000. 35 O R/W Adjusted Gain value of CH2 36 O R/W Adjusted Gain value of CH3 37 O R/W Adjusted Gain value of CH4 Adjusted Offset Value, Adjusted Gain Value: Note1:

When using Mode 2, the channel do NOT provide setups for adjusted Offset or Gain value. Note2: When output mode changes, the adjusted Offset or Gain value automatically returns to defaults. 40 O R/W Function: Set value changing prohibited Prohibit set value changing in CH1 ~ CH4. Default= H’0000. 41 X R/W Function: Save all the set values Save all the set values. Default =H’0000. 43 X R Error status Register for storing all error status. Refer to table of error status for more information. 100 O R/W Function: Enable/Disable limit detection Upper and lower bound detection, b0~b3 corresponds to CH1~CH4 (0: Disable/ 1: Enable). Default= H’0000.

101 X R/W Upper and lower bound status Display the upper and lower bound status. (0: Not exceed /1: Exceeds upper or lower bound value), b0~b3 corresponds to Ch1~Ch4 for lower bound detection result; b8~b11 corresponds to CH1~CH4 for upper bound detection result.. 102 O R/W Set value of CH1 upper bound Set value of CH1~CH4 upper bound. Default = K32000. 103 O R/W Set value of CH2 upper bound 104 O R/W Set value of CH3 upper bound 105 O R/W Set value of CH4 upper bound 108 O R/W Set value of CH1 lower bound Set value of CH1~CH4 lower bound. Default = K-32000.

109 O R/W Set value of CH2 lower bound 110 O R/W Set value of CH3 lower bound 111 O R/W Set value of CH4 lower bound 114 O R/W Output update time of CH1 Set value of CH1~CH4 lower bound. Setting range: K0~K100. Default =H’0000. 115 O R/W Output update time of CH2 116 O R/W Output update time of CH3