Chapter 5 CPU and Module Devices Adjust D/A Conversion Curve You can adjust the conversion curves according to the actual needs by changing the Offset value (CR#32 ~ CR#33) and Gain value (CR#38 ~ CR#39). Offset: The corresponding voltage/current input value when the digital output value = 0. Gain: The corresponding voltage/current input value when the digital output value = 16,000. Equation for voltage output Mode0: ( ) ( ) Ч + − Ч = 32000 ) ( 10 16000 V Offset Offset Gain X V Y Y=Voltage output, X=Digital input Resolution: 0.3125mV = 20V/64,000 Equation for current output Mode1:
( ) ( ) Ч + − Ч = 32000 ) ( 20 16000 mA Offset Offset Gain X mA Y Y=Current output, X=Digital input 5_ Resolution: 0.625μA = 20mA/32,000 Equation for current input Mode2: ( ) ( ) Ч + − Ч = 32000 ) ( 20 6400 16000 6400 19200 mA X mA Y Y=Current output, X=Digital input Resolution: 0.5μA = 16mA/32,000 5-33 Mode 0 of CR#2 ~ CR#5 -10V ~ +10V, Default: Gain = 16,000(= ), Offset = 0 R ange of digital conversion -32,000 ~ +32,000 c Max./Min. range of digital -32,768 ~ +32,767 onversion