Delta Electronics DVP-ES3 — 5.3.5 DVP04TC-E2 Control Registers

DVP-ES3 Series Operation Manual 5.3.5 DVP04TC-E2 Control Registers _5 5-40 CR# Attrib. Register content Description 0 O R Model name Set up by the system: DVP04TC-E2 model code = H’0083 1 O R Firmware version Display the current firmware version in hex. 2 O R/W CH1 Input mode setting Input mode: Default = H’0000. Take CH1 for example: Mode 0 (H’0000): J-type (-100°C ~1,150°C) Mode 1 (H’0001): K-type (-100°C ~ 1,350°C) Mode 2 (H’0002): R-type (0°C ~ 1,750°C) Mode 3 (H’0003): S-type (0°C ~ 1,750°C) Mode 4 (H’0004): T-type (-150°C ~ 390°C) Mode 5 (H’0005): E-type (-150°C ~ 980°C) Mode 6 (H’0006): N-type (-150°C ~ 1,280°C) Mode 7 (H’0007): -80mV~+80mV Mode -1(H’FFFF):

Close 3 O R/W CH2 Input mode setting 4 O R/W CH3 Input mode setting 5 O R/W CH4 Input mode setting 7 O R/W Temperature unit setting Select the temperature unit (Celsius °C / Fahrenheit °F). Default = H0(°C) 8 O R/W CH1 sampling range Set sampling range at CH1 ~ CH4 Range = K1 ~ K100 Default = K10 9 O R/W CH2 sampling range 10 O R/W CH3 sampling range 11 O R/W CH4 sampling range 12 X R Average temperature measured at CH1 Average temperature measured at CH1 ~ Ch2 Temperature unit: set in CR#7 13 X R Average temperature measured at CH2 14 X R Average temperature measured at CH3 Average temperature measured at CH3 ~ Ch4 Temperature unit:

set in CR#7 15 X R Average temperature measured at CH4 20 X R Present temperature measured at CH1 Present temperature measured at CH1 ~ CH4 Temperature unit: set in CR#7 21 X R Present temperature measured at CH2 22 X R Present temperature measured at CH3 23 X R Present temperature measured at CH4 28 O R/W Adjusted Offset value of CH1 Set the adjusted Offset value of Ch1 ~ Ch4. Default = K0 Range: K-400 ~ K400 Temperature unit: set in CR#7 Definition of Offset at Ch1 ~ Ch4 in DVP04TC-E2: Deviation digital value from the target value. 29 O R/W Adjusted Offset value of CH2 30 O R/W Adjusted Offset value of CH3 31 O R/W Adjusted Offset value of CH4 40 O R/W Function:

Set value changing prohibited Prohibit set value changing in CH1 ~ CH4 41 X R/W Function: Save all the set values Save all the set values, Default =H’0000 43 X R Error status Register for storing all error status. See the table of error status for more information. 100 O R/W Function: Enable / Disable limit detection Upper and lower bound detection, b0~b3 corresponds to CH1 ~ CH4 (0: Disable/ 1: Enable). Default= H’0000.