Delta DVP-ES3 — 5.3.5 DVP04TC-E2 Control Registers

DVP-ES3 Series Operation Manual  Adjust PT Conversion Curve You can adjust the conversion curves according to the actual needs by changing the Offset value (CR#28 ~ CR#31). Offset: The corresponding voltage/current input value when the digital output value = 0.  Mode0 ~ Mode6: output unit 0.1°  − ° ° = Offset X Y ) ( . ) ( 1 0        _5 Y= Digital output, X= Measured temperature input  Mode7: 0.01 mV = 80 mV/8000  − = Offset V V X Y ) m ( . ) m ( 01 0        Y= Digital output, X= Current input 5-42 CR Attrib. Register content Description 132 152 172 192 X R Output width (ms) Width of control output. Unit: ms 133 153 173 193 X R Output cycle (ms) Cycle of control output.

Unit: ms 134 154 174 194 X R Output volume Output volume 135 155 175 195 X R/W PID RUN/STOP _ 0: STOP, 1: RUN. Default = K0 136 156 176 196 X R/W Auto-tuning 0: Disabled, 1: Auto-tuning. Default = K0 Symbols: O: Set value will be saved. X: Set value will not be saved. R: You can use FROM instruction to read data. W: You can use TO instruction to write data.

-100°C ~ 1150°C (-1000~11500) -148°F ~ 2102°F (-1480~21020) Mode 0 of CR#2~ CR#5 -100°C ~ 1350°C (-1000~13500) -148°F ~ 2462°F (-1480~24620) Mode 1 of CR#2~ CR#5 0°C ~ 1750°C (0~17500) 32°F ~ 3182°F (320~31820) Mode 2, 3 of CR#2~ CR#5 -150°C ~ 390°C (-1500~3900) -238°F ~ 734°F (-2380~7340) Mode 4 of CR#2~ CR#5 -150°C ~ 980°C (-1500~9800) -238°F ~ 1796°F (-2380~17960) Mode 5 of CR#2~ CR#5 -150°C ~ 1280°C (-1500~12800) -238°F ~ 2336°F (-2380~23360) Mode 6 of CR#2~ CR#5 Offset (CR#34 ~ CR#37) Deviation digital value corresponds to 0°C/ °F