DVP-ES3 Series Operation Manual (4) Make sure that the summary in the CARD Utility wizard is consistent with the data restoration you want to perform and then click Execute . If you click Cancel in the process of restoring data to the DVP-ES3 Series CPU module, the data is not completely restored. The DVP-ES3 Series CPU module still performs the data restoration even if you click Cancel in the process of restoring a backup file in the memory card. You can turn off the DVP-ES3 Series CPU module to stop the data restoration from being performed.
To prevent the DVP-ES3 Series CPU module from operating incorrectly, restore the DVP-ES3 Series CPU module to the factory setting, or perform the data restoration again. The restoration source or restoration destination may contain a password and an ID. The following table describes the password and the ID process. _7 (5) After you perform the data restoration, click Home or Close in the CARD Utility wizard. 7-16 Data restoration Description Memory card PU module a. The ID in the backup file must be the same as the ID in the CPU module; otherwise the data is not restored. b.
If there is a PLC password in the CPU module, the password in the backup file must be the same as the PLC password in the CPU module. Otherwise the data is not restored. c. If there is no PLC password in the CPU module, and there is a password in the backup file, the system restores the data, and the password in the backup file becomes the PLC password in the CPU. Computer ISPSoft project The ID and the password in the backup file become the program ID and the project password in the ISPSoft project.