Delta DVP-ES3 — 9.1.3.1 Delta EIP Architecture

Chapter 9 Ethernet Specification and Operation 9.1.3 Ethernet Features 9.1.3.1 Delta EIP Architecture This typical Delta EIP architecture includes an EIP Scanner and Adapters; data mapping is achieved between devices through an I/O connection and explicit messaging. The DVP-ES3 Series supports single port Ethernet; thus you can install and configure devices with embedded switch technology over EtherNet/IP. 9_ 9-5 EDS Electronic Data Sheets: EDS files are simple text files used by EtherNet/IP network configuration tools to help you identify EtherNet/IP products and easily commission them on a network.

Data Mapping Exchanging data between devices EIP Scanner The master station is called an EIP Scanner in EtherNet/IP. EIP Adapter The slave station is called an EIP Adapter in EtherNet/IP. DLR Device Level Ring (DLR) provides fault-tolerant network design for daisy-chain and linear topology. The DLR protocol provides high network availability in a ring topology. It was intended primarily for implementation in EtherNet/IP end-devices that have two Ethernet ports and embedded switch technology, providing fast network fault detection and reconfiguration to support the most demanding control applications. Modbus TCP This is a Modbus variant used for communications over TCP/IP networks.