DVP-ES3 Series Operation Manual _9 9-24 Category Error Code Description How to fix them EDS file are mismatched. 2. Reload the EDS file. 3. Ask the vendor of the device for the EDS file. H’11010126 The configuration size parameters in the EDS file are mismatched. 1. Check if the product information and the EDS file match. 2. Reload the EDS file. 3. Ask the vendor of the device for the EDS file. H’11010129 The configuration path parameters in the EDS file are mismatched. 1. Check if the product information and the EDS file match. 2. Reload the EDS file. 3. Ask the vendor of the device for the EDS file. H’11010132 The EDS file does not support Null forward open. 1.
Check if the product information and the EDS file match. 2. Reload the EDS file. 3. Ask the vendor of the device for the EDS file. Data Exchange Setup Error H’12010100 I/O connections duplicated 1. Check if the system has created the I/O connections. 2. Change the connection type to Listen Only. H’12010106 Ownership conflict 1. Check the scanner owner. 2. Reconfigure the invalid scanner. 3. Change the connection to multicast. H’12010110 Target for connection not configured 1. Check the I/O connection status. 2. Activate the I/O connections again. H’12010111 Adapter RPI not supported Check the RPI for the adapter. H’12010113 Out of connections 1.
Check if the number of connections exceeds the limit. 2. Reduce the number of the product connections. H'12010119 Non-Listen only not opened 1. Check if the system has created the I/O connections. 2. Check the scanner I/O connection status. H’12010127 Invalid originator to target Size Check the module number and the product setup file to see if they match. H’12010128 Invalid target to originator Check the output size in the connection parameters.