Chapter 9 Ethernet Specification and Operation 9.6.4.5 Data Mapping In the Controller Organizer, you can map data, including Configuration, Input and Output parameters. When you create a device I/O Configuration, the tags are added automatically. Click Program TAGs to display the Tags window. Tags are listed in the Name column. Tag names begin with a product name and end with C or I1 or O1 , separated from the name by a colon (:), for example CMCEIP01:C, CMCEIP01:I1, and CMCEIP01:O1. Tag name : C indicates the tag contains information from the Adapter EDS file, including Input and Output parameters. You can edit these parameters in Studio 5000.
Tag name : I1 indicates that the mapping starts from TAG : I1[0], and is mapped to the first parameters of the Adapter output. The length is the output length provided by the Adapter. Tag name: O1, indicates that the mapping starts from TAG : O1[0], and is mapped to the first parameters of the Adapter Input. The length is the input length provided by the Adapter. Delta Adapter VFD-C2000 RA EIP Scanner 1756-L71+1756-EN2TR EtherNet/IP 9_ 9-37 Tag:I1 Tag:I1[0] Parameter 0 _ Adapter Output Tag:I1[1] Parameter 1 _ ... ... Tag:I1[31] Parameter 31 _ Tag:O1 Tag:O1[0] Parameter 0 _ Adapter Input Tag:O1[1] Parameter 1 _ ... ... Tag:O1[31] Parameter 31 _