Chapter 10 CANopen Function and Operation You can read emergencies from a slave through a PLC ladder diagram. 6. It supports the SYNC object (synchronous object) service. 7. Several devices can operate synchronously through the synchronous object service. 8. The supported CANopen communication rates are: 20K, 50K, 125K, 250K, 500K, and 1Mbps. The supported mapping data types are: The CAN port has the following functions when acting as a slave. It supports the standard CANopen protocol DS301 V4.02. It supports the NMT (network management object) service. It supports the NMT state control. The state of the DVP-ES3 Series in the CANopen network is controlled by a master.
It supports the NMT error control. The DVP-ES3 Series supports Heartbeat but not Node Guarding. It supports the PDO (process data object) service. The PDO message transmits the immediate input data and output data. It supports up to 8 TxPDO and 8 RxPDO. The PDO transmission type: synchronous mode and asynchronous mode It supports the emergency service. If an error or an alarm occurs in the DVP-ES3 series, the master is notified through the emergency service. 10.1.2 The Input/Output Mapping Areas The following table lists the CANopen DS301 specifications for the AS DVP-ES3 Series PLC.
10 10-3 Storage Data type 8-bit SINT USINT BYTE 16-bit INT UINT WORD 32-bit DINT UDINT REAL DWORD 64-bit LINT ULINT LREAL LWORD Type Item Description Master Maximum slave nodes Up to 64 nodes Maximum transfer size of a PDO (Read + Write) Up to 2000 Bytes (including some system configurations) Slave Maximum transfer size of a PDO (Read + Write) Up to 8 PDOs; each PDO with up to 8 bytes can be transferred at a time