Delta Electronics DVP-ES3 — 10.3.2 The CANopen Communication Object

DVP-ES3 Series Operation Manual The control message format for the node state: The command specifiers:  Error control services The error control service detects the disconnection of a network node. The error control services are classified into two types: Heartbeat and Node Guarding. The DVP-ES3 Series PLC only supports Heartbeat. For example, the master can detect the disconnection of the slave only after the slave enables the Heartbeat service. The following illustrates the Heartbeat principle. The Heartbeat producer transmits the Heartbeat message according to the set Heartbeat producing time. One or many Heartbeat consumers detect the message transmitted by the Heartbeat producer.

If the consumer does not receive the message transmitted by the producer within the timeout period, there is a problem in the CANopen communication or the producer is disconnected. Heartbeat consumer Request Request Heartbeat timeout period _10 Heartbeat event 10-16 COB-ID Byte 0 Byte 1 0 Command specifier (CS) Slave address (0: Broadcast) Command specifier Function (Hex) 01 Start the remote node 02 Stop the remote node 80 Enter the pre-operational state 81 Reset the application layer 82 Reset the communication Heartbeat producer Receiving Receivin Receivin g Receiving Heartbeat timeout period artbeat Heartbeat producing time