DVP-ES3 Series Operation Manual An Emergency 1 consists of the data in D6004-D6007 and every Emergency message consists of 8 bytes of data. The following table shows the data format of Emergency messages on the CAN bus. Datum 0–datum 7 in Emergency response message correspond to byte 0–byte 7 respectively. Example 1: read the Emergency message from the slave No.2, and the Emergency messages the slave sends out successively. Request data:
Emergency response data _10 10-24 COB-ID Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 80 (Hex) +Node-ID Emergency error code Error storage register Vendor custom error code COB-ID Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 82 (Hex) 43 54 20 14 0 0 0 0 COB-ID Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 82 (Hex) 42 54 20 15 0 0 0 0 Request message PLC device High byte Low byte D25000 Message header ReqID=01 Command =01 D25001 Reserved Size =0 D25002 Type =04 Node ID =03 Response message PLC device High byte Low byte D24000 Message header ResID=01 Status code =01 D24001 Reserved =0 Size =2A (Hex) D24002 Type =04 Node ID =03 D24003 Message data Total number of data =1 Number of data stored =1 D24004 Datum 1=54 Datum 0=42 D24005 Datum 3=20 Datum 2=14 D24006 Datum 5=0 Datum 4=0 D24007 Datum 7=0 Datum 6=0