DVP-ES3 Series Operation Manual Note : Synchronous transmission type can fulfill multi-axis motion at the same time. If you monitor a real-time changing parameter such as the actual rotation speed of the motor, set the TxPDO to the synchronous transmission type; otherwise the frequent change in the slave data can block the CANopen network. After you finish setting the above parameters, double click the master device to display the Node List Setting dialog box. Select ASDA-A2 Drive, and click > to move the A2 drive to the right-side list, and then download the configured data. The mapping relation between master and slave:
_10 10-36 Transmission Type Description Remark TxPDO The slave sends out the data once every one Event timer time. After that, the TxPDO data is not allowed to be sent out within an inhibit timer time. When the Event timer and Inhibit timer are both equal to 0, the slave sends TxPDO data to the master immediately when the data changes, and the data that master receives is immediately valid. 255 Same as Type254 DVP-ES3 Series PLC master Data transmission on CANopen A2 device register bus Low word of P1-09 of D25032 servo D25033 High word of P1-09 of servo D25034 P3-06 of servo D25037 P4-07 of servo D24032 Low word of P0-09 of servo D24033 High word of P0-09 of servo