DVP-ES3 Series Hardware Manual C.1 EMC Standards for an AS Series System C.1.1 DVP-ES3 Series System EMC Standards The EMC standards that are applicable to a DVP-ES3 series system are listed in the following tables.
EMI EMS _C C-2 Port Frequency range Level (Normative) Reference standard Enclosure port ) 30-230 MHz 40 dB (μV/m) quasi-peak IEC 61000-6-4 (radiated) 230-1000 MHz 47 dB (μV/m) quasi-peak (measured at a distance of 10 meters AC power port (conducted) 0.15-0.5 MHz 79 dB (μV) quasi-peak IEC 61000-6-4 66 dB (μV) average 0.5-30 MHz 73 dB (μV) quasi-peak 60 dB (μV) average Environmental Reference Test Test level phenomenon standard Electrostatic IEC 61000-4-2 Contact ± 4 kV discharge Air ± 8 kV Radio frequency electromagnetic field Amplitude modulated IEC 61000-4-3 80% AM, 1 kHz sinusoidal 2.0-2.7 GHz 1 V/m 1.4-2.0 GHz 3 V/m 2.0-2.7 GHz 3 V/m 2.7-6.0 GHz 3 V/m Power frequency IEC 61000-4-8 60 Hz 30 A/m magnetic field 50 Hz 30 A/m