DVP-ES3 Series Hardware Manual _D D-6 No. Item Inspection Criterion Remedy module. 3 Installation Looseness Check whether the module is loose. The module must be installed firmly. Please refer to Chapter 2 for more information on installing the module. Adhesion of dirt Check the appearance. Dirt must not be present. Remove the dirt. 4 Connection Looseness of terminal screws Tighten the screws with a screwdriver. The screws must not be loose. Tighten the screws. Looseness of connectors Pull the connectors. The connectors must not be loose. Tighten the screws on the connectors. 5 PLC system diagnosis Check the error logs. No new error occurs. Please refer to Section 9.1.3 for more information.
6 Maximum scan time Check the states of SR413 and SR414 through the device monitoring table in ISPSoft. The maximum scan cycle must be within the range specified in the system specifications. Determine why the scan time exceeds specifications.