Delta DVP-ES3 — 2.5.2 Temperature Measurement Module Profiles

Chapter 2 Specifications and System Configuratio n 2_ 2.5.2 Temperature Measurement Module Profiles 1 4 5 6 2 7 8 9 3 Unit: mm 2-24 S-type:K0 ~ K17,500 T-type:K-1,500 ~ K3,900 E-type:K-1,500 ~ K9,800 N-type:K-1,500 ~ K12,800 S-type:K320 ~ K31,820 T-type:K-2,380 ~ K7,340 E-type:K-2,380 ~ K17,960 N-type:K-2,380 ~ K23,360 n 16-bit (0.1°C) 16-bit (0.1°F) 16-bit (0.01 mV) Hardware resolutio Average function Yes, CR#8 ~ CR#11, setting range:

K1 ~ K100 Self-diagnosis Detecting if exceeding upper and lower limts or channel disconnection function An analog circuit is isolated from a digital circuit by a digital integrated circuit/an optocoupler, and the analog channels are isolated from one another by optocouplers. Isolation between a digital circuit and a ground: 500 VDC Isolation between an analog circuit and a ground: 500 VDC Isolation between an analog circuit and a digital circuit: 500 VDC Isolation between the 24 VDC and a ground: 500 VDC Isolation between analog channels: 120 VAC Isolation 0 4PT- E2 4AI-PT Number Name Description The inputs are connected to sensors.

1 Removabl e terminal block The outputs are connected to loads to be driven. External m 2 port odule connection Connects the modules 3 Terminal n umber Terminal number 4 Model nam e Model name of the module Indicates the status of the power supply 5 POWER L ED indicator ON: the power is on OFF: no power