DVP-ES3 Series Operation Manual 4.5 Connecting Power Cables 4.5.1 Precautions  Connecting AC power cables (1) The cables carrying the 110 VAC, 220 VAC, and 24 VDC should be single or two-wire cables. (2) Do not bundle 110 VAC cable, 220 VAC cable, 24 VDC cable, the (high-voltage high-current) main circuit, and the I/O signal cable together. The distance between adjacent cables should be more than 100 millimeters (3.94 inches). (3) To prevent electrical surge from lightning, install a surge protector as shown below. Surge absorber AC power supply 100-240V _4 Points for attention: 1. Ground the surge protector and the PLC system. 2.

Select the surge protector with a working voltage that is not less than the maximum allowable input voltage. 4.5.2 Ground  The diameter of the ground should not be less than the diameters of the cables connected to the terminals L and N.  If using multiple pieces of equipment, use a single-point ground. DVP-ES3 CPU Module Another piece of equipment The single-point ground is better.  If you cannot use a single-point ground, use a common-point ground. DVP-ES3 CPU Module Another piece of equipment The common-point ground is permitted.  Do not connect equipment ground wires together as shown on the right.

DVP-ES3 CPU Module Another piece of equipment The equipment can not be grounded in this way. 4-10 DVP-ES3 CPU Module DVP-ES3 CPU Module