DVP-ES3 Series Operation Manual 4.7.5 Wiring DVP08XP211T _4 Note: You need to add external power supply 24 VDC (-15% ~ +20%) for UP and ZP; power consumption is up to 5 mA. 4-24 Input form Direct current (sinking or sourcing) Voltage specifications 24 VDC, 5 mA Output type Transistor-T (sinking) Voltage specifications 5 to 30 VDC, 0.5A/output, 4A/COM Sinking input and output Sourcing input and sinking output IN S/S X0 X1 X2 X3 NC DVP08XP211T ( 4DI/4DO) UP ZP Y0 Y1 Y2 Y3 OUT IN S/S X0 X1 X2 X3 NC DVP08XP211T ( 4DI/4DO) UP ZP Y0 Y1 Y2 Y3 OUT S/S X0 X1 X2 X3 NC DVP08XP211T ( 4DI/4DO) UP ZP Y0 Y1 Y2 Y3 S/S X0 X1 X2 X3 NC DVP08XP211T ( 4DI/4DO) UP ZP Y0 Y1 Y2 Y3