Delta DVP-ES3 — 4.7.10 Wiring DVP16XP211T

Chapter 4 Installing Hardware 4.7.10 Wiring DVP16XP211T 4_ Note: 1. You need to add external power supply 24 VDC (-15% ~ +20%) for UP and ZP; power consumption is up to 15 mA. 2. Connect the terminal to ground.

4-29 Input form Direct current (sinking or sourcing) Voltage specifications 24 VDC, 5 mA Output type Transistor-T (sinking) Voltage specifications 5 to 30 VDC, 0.5A/output, 4A/COM IN S/S X0 X1 X2 X3 X4 X5 X6 X7 NC DVP16XP211T ( 8DI/8DO) UP ZP Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 NC OUT Sinking input and output IN S/S X0 X1 X2 X3 X4 X5 X6 X7 NC DVP16XP211T ( 8DI/8DO) UP ZP Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 NC OUT Sourcing input and sinking output S/S X0 X1 X2 X3 X4 X5 X6 X7 NC UP ZP Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 NC S/S X0 X1 X2 X3 X4 X5 X6 X7 NC UP ZP Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 NC