Delta DVP-ES3 — 6.27.2 Explanation of CANopen Communication Instructions

Chapter 6 Applied Instructions Symbol S 1 : Station address of a servo S 2 Target speed Explanation 6_ 1. This instruction executes the servo speed control for the servo at the address specified in S 1 . The INITC and ASDON (Servo ON) instructions must be complete before this instruction is executed. 2. The range of S 1 is 1–8 (for servo) and 21-28 (for inverter). There will be no execution when the input value is out of the range. 3. Table to describe S 2 4. For corresponding SM and SR of the axes, refer to the DRVIC instruction (API 2803). 5. SM1682 is set to ON when an error occurs during communication.

In addition, SR658 retains the number of the axis in which the error occurs and SR659 retains the error code. 6-895 API Instruction Operand Description 2805 D PLSVC S1, S2 Servo speed control Device X Y M S T C HC D FR SM SR E K 16# “$” F S1    S2     BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S1   S2   Pulse instruction 16-bit instruction 32-bit instruction - - ES3 Servo type Range of S1 Range of S2 Descriptions of S2 Servo 1-8 -60000 - 60000 (0.1rpm) The +/- sign indicates the forward / reverse direction. For example, when inputting 6005 in S2, the value is 600.5rpm.

Inverter 21-28 -32768 - 32767 (1rpm) The +/- sign indicates the forward / reverse direction. For example, when inputting 605 in S2, the value is 605rpm.