DVP-ES3 Series Programming Manual 6.27.3 Frequently asked questions in Delta special CANopen communication and Troubleshooting Question 1: After the PLC starts the INITC instruction, the initialization completion flag SM1681 is not set to ON. Steps: 1) Make sure that CANopen communication mode is Delta special driver or Delta special driver & CANopen DS301 mode. Then check if the communication rate is the specified baud rate. After above settings are correct, re-download the hardware configuration table and then re-check if the initialization works. If the initialization still does not work, proceed with the next step. 2) Ensure that the servo initialization has been set by manual.
Then re-power the servo on after power off. After doing so, continue with step 3. 3) Ensure that the servo node ID (P3-00), baud rate and mode (P3-01) have been set by manual and communication mode (P1-01) has been set to PR mode by manual. Then proceed with the step 4. 4) Ensure that the CAN communication cable connection is proper, the terminal resistor in ES3 Series PLC is switched on and the last servo has been connected with a terminal resistor. Then move forward to the step 5. 5) Observe whether the word: code appears temporarily on the digital display of the servo when the PLC enables the initialization instruction.
If there is no code appearing temporarily, return to step 1 or replace the servo. If there is the word code appearing temporarily, go to step 6. 6) Check if the actual states of DI0~DI7 (P2-10 ~ P2-17) of the servo are consistent with the function settings of servo parameters. E.g. DI0 is the negative limit input (contact A). Check if the actual input state has been OFF (Contact B). If DI function has been enabled, make the function disabled. If the function has not been enabled, _6 go on with step7. 7) The communication mode is switched back to CANopen DS301 mode. Use the CANopen Builder software to search the slave and observe which slave has not been scanned.
Remove the one which has not been scanned and then make the initialization again by adjusting the servo node ID and the ID in INITC in the PLC. 6-920