Delta DVP-ES3 — 3.4.1 Applied Instructions (Sorted Numerically by API number)

Chapter 3 Instruction Tables 3_  Arithmetic instructions 3-15 API Instruction code Pulse Symbol Function 16-bit 32-bit Instruction 0076 ANDZ DANDZ ─ Comparing the absolute result of the contact type ON: | S1- S2|<| S3| OFF: | S1- S2|≧ | S3| 0077 ANDZ DANDZ ─ Comparing the absolute result of the contact type ON: | S1- S2|≦| S3| OFF: | S1- S2|>| S3| 0078 ORZ= DORZ= ─ Comparing the absolute result of the contact type ON: | S1- S2|=| S3| OFF: | S1- S2| ≠ | S3| 0079 ORZ DORZ ─ Comparing the absolute result of the contact type ON: | S1- S2| ≠ | S3| OFF: | S1- S2|=| S3| 0080 ORZ> DORZ> ─ Comparing the absolute result of the contact type ON: | S1- S2|>| S3| OFF:

| S1- S2| ≦ | S3| 0081 ORZ>= DORZ>= ─ Comparing the absolute result of the contact type ON: | S1- S2| ≧ | S3| OFF: | S1- S2|<| S3| 0082 ORZ DORZ ─ Comparing the absolute result of the contact type ON: | S1- S2|<| S3| OFF: | S1- S2| ≧ | S3| 0083 ORZ DORZ ─ Comparing the absolute result of the contact type ON: | S1- S2| ≦ | S3| OFF: | S1- S2|>| S3| Instruction code 16-bit 32-bit Pulse API Symbol Function 32-bit instruction 0100 + D+  Adding binary numbers S1+S2=D