DVP-ES3 Series Programming Manual 5.1 List of Basic Instructions The following table lists the Basic instructions covered in this chapter.
_5 5-2 Operation Instruction code Function Operand time (µs) LD/AND/OR Loading contact A/Connecting contact A in series/Connecting contact A in parallel DX, X, Y, M, SM, S, T, C, HC, D 0.025 LDI/ANI/ORI Loading contact B/Connecting contact B in series/Connecting contact B in parallel DX, X, Y, M, SM, S, T, C, HC, D 0.03 OUT Driving the coil DY, Y, M, SM, S, T, C, HC, D 0.04 SET Keeping the device on DY, Y, M, SM, S, T, C, HC, D 0.04 MC/MCR Setting/Resetting the master control N 0.24 LDP/ANDP/ORP Starting the rising-edge detection/Connecting the rising-edge detection in series/Connecting the rising-edge detection in parallel DX, X, Y, M, SM, S, T, C, HC, D 0.22 LDF/ANDF/ORF Starting the falling-edge detection/Connecting the falling-edge detection in series/Connecting the falling-edge detection in parallel DX, X, Y, M, SM, S, T, C, HC, D 0.22 PED/APED/OPED Starting the rising-edge detection/Connecting the rising edge-detection in series/Connecting the rising-edge detection in parallel X, Y, M, SM, S, T, C, HC, D 0.22 NED/ANED/ONED Starting the falling-edge detection/Connecting the falling-edge detection in series/Connecting the falling-edge detection in parallel X, Y, M, SM, S, T, C, HC, D 0.22 PLS Rising-edge output Y, M, SM, S, D 0.22 PLF Falling-edge output Y, M, SM, S, D 0.22 INV Inverting the logical operation result – 0.22 NP The circuit is rising edge-triggered.
– 0.24 PN The circuit is falling edge-triggered. – 0.24 FB NP The circuit is rising edge-triggered. Y, M, S, D 0.24 _ FB PN _ The circuit is falling edge-triggered. Y, M, S, D 0.24