Delta DVP-ES3 — 6.4.2 Explanation of Data Transfer Instructions

Chapter 6 Applied Instructions Symbol S : Data source n : Data length D : Data destination Explanation 1. This instruction transfers n pieces of data in devices starting from the device specified by S to the devices starting from the device specified by D . 6_ 2. When S is T, C or HC, the instruction transfers only the state of the device, but does not transfer the current value of the device. 3. The value in n must be between 1–256. When n not between 1–256, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. Example When M0 is ON, the instruction transfers the data in D0.8–D0.13 to D1.2–D1.7.

6-147 API Instruction code Operand Function 0310 MOVB P S, n, D Transferring bits in blocks Device X Y M S T C HC D FR SM SR E K 16# “$” F S          n         D     BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S  n    D  Pulse instruction 16-bit instruction 32-bit instruction ES3 ES3 -