DVP-ES3 Series Programming Manual Symbol D : First device for the shift n : Data length Explanation 1. This instruction shifts the data in the n registers starting from D to the right, and clears the data in D + n -1 to 0. 2. In general, the NSFRP pulse instruction is used. _6 3. The operand n must be between 1–512. Example When M0 is ON, the instruction shifts the data in D1–D6 to the right, and clears the data in D6 to 0.
D6 D0 D1 D2 D3 D4 D5 After the shift D6 D0 D1 D2 D3 D4 D5 Being cleared to 0 6-338 API Instruction code Operand Function 1114 NSFR P D, n Shifting n registers to the right Device X Y M S T C HC D FR SM SR E K 16# “$” F D n BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type D n Pulse instruction 16-bit instruction 32-bit instruction ES3 ES3 - 30 2235 9578 754 28 423 11 0 30 2235 9578 754 28 423