DVP-ES3 Series Programming Manual Example Suppose the value in D0 is 16#1234. When M0 is enabled, the instruction divides the value in D0 into four groups (four bits in a group), and stores these groups in the low four bits in every register (the registers range from D10 to D13.). b3 b0 b7 b4 b11 b8 b15 b12 b3 b0 b15 b4 D0 D10 D11 D13 D12 All becomes 0. The positions in whcih the data is stored. _6 Additional remarks 1. If D – D +( n -1) exceed the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. If n is not between 1–4, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. 6-378 1 2 3 4 4 4 3 2 1