DVP-ES3 Series Programming Manual Example Suppose the values in D0 – D3 are 16#1234, 16#5678, 16#8765, and 16#4321 respectively. When M0 is enabled, the UNI instruction divides the values in D0–D3 into groups (four bits in a group), and stores every group in b0 – b3 in D10(b0–b15). D0 b3 b0 b15 b4 D2 D1 D3 D10 _6 b3 b0 b7 b4 b11 b8 b15 b12 Additional remarks 1. If S to S +( n -1) exceed the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. If n not between 1 – 4, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. 6-380 1 2 3 4 1 5 8 4 5 6 7 8 8 7 6 5 4 3 2 1 1 5 8 4