Delta DVP-ES3 — 6.13.2 Explanation of Data Processing Instructions

DVP-ES3 Series Programming Manual If the minimum output value in S 1 is larger than the maximum output value in S 2 , the instruction is not executed. 2. Only the 32-bit instructions can use the 32-bit counter, but not the device E. Example  When M0 is ON, the instruction compares the value in D0 with 500 and 5000, and stores the comparison result in D1. _6 Additional remarks If the minimum output value in S 1 is larger than the maximum output value in S 2 , the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 6-384 Minimum output Maximum output Output value in D0 Function Output value in D1 value value 500 5000 499 D0 500 5001 D0>5000 5000 600 500≦D0≦5000 600