Delta DVP-ES3 — 6.19.2 Explanation of Communication Instructions

DVP-ES3 Series Programming Manual _6 Symbol S 1 : Baud Rate (Unit:100 bps) S 2 : Number of data bits S 3 : Parity bit S 4 : Number of end bits S 5 : Modbus format selection D : Communication port number Explanation 1. This instruction provides a way to directly set the parameter values, instead of declaring variables. 2. S 1 sets the baud rate with the units 100 bps. For example, a value 96 indicates 9600 bps. 3. S 2 sets the number of data bits. The value 7 indicates 7 data bits and 8 indicates 8 data bits. If the value is not 7 or 8 in S 2 , the instruction uses the default value.

6-564 API Instruction code Operand Function 1813 COMDF P S1, S2, S3, S4, S5, D Setting the communication format for a serial communication port Device X Y M S T C HC D FR SM SR E K 16# “$” F S1   S2   S3   S4   S5   D   BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S1 S2 S3 S4 S5 D Pulse instruction 16-bit instruction 32-bit instruction ES3 ES3 -