Delta DVP-ES3 — 6.19.2 Explanation of Communication Instructions

DVP-ES3 Series Programming Manual 4. The following chart shows the timing for sending and receiving data. _6 Enable/disable t he execution of the instruction Sending data Reception fl ag Receiving data Compl etion fl ag   Description:   Start or stop the execution of the instruction.   Transmitting data begins. During this time, the communication timeout time is not measured.   The reception flag is set. From the moment when the first character is received to the moment when the next 6-568 S3 S3 function name S source and received data Remark function code 1 Clockwise running command Velocity value Refer to AC motor drive user manual for the setting value and the unit.

2 Counterclockwise running command Velocity value 3 Stop Unused Any value can be stored in S. 4 Jog clockwise running command Unused Refer to AC motor drive user manual for setting the jog velocity. 5 Jog counterclockwise running command Unused 6 Reading the state Received state values Refer to AC motor drive user manual for the meaning of the state values of the 5 bit addresses H2100–H2104 for VFD.        