Delta DVP-ES3 — 6.19.2 Explanation of Communication Instructions

DVP-ES3 Series Programming Manual 5. S 7 is the length of written data with the unit of byte. 6. S 8 is the starting address of the devices where written data are stored in the order from low bit to high bit. 7. S 9 is the communication timeout time. The range of the setting value is 1~100 and the unit is 0.1s (second). 8. S 10 is the number of retransmission times and the range is 0~3. When the communication timeout occurs, the communication will be transmitted again. 9. D 3 displays the read or write error code. 10. D 4 is the read data length with the unit of byte. 11. D 5 is the starting address of the devices where read data are stored in the order from low bit to high bit. _6 12.

D 1 is the communication completion flag and D 2 is the error flag. See the detailed communication sending procedure and sequence diagram.  The DNETRW instruction is enabled for the first time and the command will be sent out immediately if the instruction is not be occupied by other DeviceNet communication.  The command is being sent.  The data sending is completed and the completion flag or error flag changes to On according to the response.  The next message is ready to be sent out. The next command is sent out right after the completion flag or error flag is cleared.  The command sending is completed and the DNETRW instruction is disabled.