Delta DVP-ES3 — 6.20.2 Explanation of Other Instructions

Chapter 6 Applied Instructions Symbol S : Delay Explanation This instruction delays the execution of the program following the DELAY instruction for a period of time specified in S . The unit of S is 0.1 milliseconds. Example 6_ When M0 is ON, the instruction delays the execution of the program following the DELAY instruction for two milliseconds. That is, Y0 is ON and the states of Y0–Y7 and Y10–Y17 are refreshed two milliseconds after the DELAY instruction is executed.

6-615 API Instruction code Operand Function 1901 DELAY P S Delaying the execution of the program Device X Y M S T C HC D FR SM SR E K 16# “$” F S         BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S    Pulse instruction 16-bit instruction 32-bit instruction ES3 ES3 ─