Delta DVP-ES3 — 6.21.2 Explanation of String Processing Instructions

Chapter 6 Applied Instructions Additional remarks 1. If the ASCII code in S is not ASCII codes 16#30–16#39, 16#20, or 16#00, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. If S is a string and the number of characters contained in the string exceeds the range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 3. For 16-bit instructions, if you declare the operand S in ISPSoft, the data type is ARRAY [2] of WORD/INT. 4. For 32-bit instructions, if you declare the operand S in ISPSoft, the data type is ARRAY [4] of WORD/INT. 6_ 6-647