Delta DVP-ES3 — 6.22.2 Explanation of Ethernet Instructions

Chapter 6 Applied Instructions 2. In general, use the MCONFP pulse instruction. 3. The following points explain the Modbus communication function codes in S 4 and S 8 . When the ES3 Series PLC reads the data from multiple bit devices (not discrete input devices), the function code sent is 1 (16#01). 6-719 Operand Name Description Data Type Remarks S7 Local register where received data is stored Function code for reading data in Bit device; M device only Function code for reading data in Word device; D device only BOOL WORD S8 Write function code Range: 16#05, 06, 0F, and 10. If the function code is out of range, outgoing parameters, including address and data length, are not modified.

WORD S9 Write remote communication address Range:16#0000–16#FFFF WORD S10 Write data length Function code 16#0F for writing Bit device, ranging from 1 to 256; the value in function code 16#05 can only be 1 or 0. Function code 16#10 for writing Word device, ranging from 1 to 100; the value in function code 16#06 can only be 1 or 0. When the setting value is 0 or less than 0, this function is not enabled. If the setting value is bigger than the maximum value, it will be seen as the maximum value. WORD S11 Local register where remote data is written Function code for writing data in Bit device; M device only Function code for writing data in Word device; D device only BOOL WORD 6 6 _