DVP-ES3 Series Programming Manual 2. Instruction flags: 3. Related error codes (SR453): _6 4. If the format of the target file on the memory card is 0, the format of the source file in the PLC must also be 0. Otherwise, the instruction cannot read the data, and SM453 is ON. The same applies to the other file formats. Example SM450 is ON when you insert the memory card into the CPU module; SM452 is ON when the MWRIT instruction executes; SM452 is OFF when the MWRIT instruction completes. You cannot use MWRITP (the pulse instruction) continuously.
Executing this pulse instruction to write data into the memory card continuously may exceed the writing limitation and may lead to memory card damage. 6-732 Flag Description SM450 ON: the memory card is in the CPU module. SM451 State of the write protection switch on the memory card ON: the memory card is write protected. OFF: the memory card is not write protected. SM452 The data is being written from the PLC to the memory card, or the data is being read from the memory card to the PLC. SM453 ON: an error occurs during the operation of the memory card. If the flag is ON, you must reset it to OFF. The error code is stored in SR453.
Error code Description 16#005E An error occurs when the memory card is initialized. 16#005F The path is incorrect, or the file does not exist. 16#0060 The default folder cannot be created. 16#0061 The memory space is insufficient. 16#0062 The memory card is write protected. 16#0063 An error occurs when the data is written into the file. 16#0064 The data cannot be read from the memory card. 16#0065 The file is a read-only file.