DVP-ES3 Series Programming Manual The default folder path: 2. Instruction flags _6 3. Related error codes (SR453): 6-742 S3 S3 +1 S3+2 'e' 'T' S3 ASCII代碼 S3 +1 S3+2 16#65 16#54 't' 's' 16#74 16#73 NUL '1' 16#00 16#31 Model name Folder path ES3 Series PLC CARD\ES3\UserProg Flag Description SM450 ON: the memory card is in the CPU module. SM451 The write protection switch on the memory card ON: the memory card is write protected. OFF: the memory card is not write protected. SM452 The data is being written from the PLC into the memory card, or the data is being read from the memory card into the PLC. SM453 ON: an error occurs during the operation of the memory card.
If the flag is ON, you must reset it to OFF. The error code is stored in SR453. Error code Description 16#005E An error occurs when the memory card is initialized. 16#005F The path is incorrect, or the file does not exist. 16#0060 The default folder cannot be created. 16#0061 The memory space is insufficient. 16#0062 The memory card is write protected. 16#0063 An error occurs when the data is written into the file. 16#0064 The data cannot be read from the memory card. 16#0065 The file is a read-only file.