DVP-ES3 Series Programming Manual 6.25.2 Explanation of Task Control Instructions Symbol S 1 : Name of the SFC POU S 2 : Function code S 3 : Device address _6 Explanation 1. This instruction runs the SFC (Sequential Function Chart) program specified by S 1 according to the function code in S 2 . 2. The instruction runs the SFC POU (Program Organization Unit) specified by S 1 only when the PLC is scanning the SFC POU. 3. The operands are described as follows. S 1 defines the name of the SFC POU.
When the designated SFC POU of S 1 executes, the instruction clears the parameters (such as SFC/STEP/ACTION/TRANSITION) for the SFC program when S 2 =0 or 1, and the SFC execution starts according to the value specified in S 2. IF S 2 =0, the system executes the SFC POU from the initial step. IF S 2 =1, the system executes the SFC POU from the designated step in S 3 . 6-754 API Instruction code Operand Function 2500 SFCRUN S1, S2, S3 SFC Run Device X Y M S T C HC D FR SM SR E K 16# “$” F S1 S2 S3 BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S1 S2 S3 Pulse instruction 16-bit instruction 32-bit instruction - ES3 -