Delta DVP-ES3 — 6.26.2 Explanation of High-speed Output Instructions

DVP-ES3 Series Programming Manual Symbol S 1 : Pulse output width S 2 : Pulse output cycle D : Pulse output device Explanation 1. This instruction specifies the pulse output width. The 16-bit instruction uses 100 us as the output unit, while the 32-bit instruction uses 1 us as the output unit. 2. S 1 (pulse output width--Duty ON) is defined as t, S 2 ( pulse output cycle time--Cycle time) is T as shown below. It is recommended that S 1 ≦ S 2 . _6 3. D only allows Y0–Y7 as the pulse output device. 4. There is no limit to how many times you can use the instruction a program. But only one output instruction that uses the same output point can be executed in the same scan cycle.

When several high-speed pulse output instructions start the same output point in the program, the PLC first performs the output based on the instruction that is executed first. 5. If S 1 ≦ 0 or S 2 ≦ 0, it is processed as 0 (the pulse output is OFF). If S 1 > S 2, it is processed as S 1 = S 2. When S 1 = S 2 and S 2 is not 0, the pulse output is always ON. 6. You can modify the pulse output width S 1 and pulse output cycle S 2 when the PWM instruction is executed. 7. The relevant special registers SR are listed in the following table.

6-772 S2      D  Pulse Instruction 16-bit instruction 32-bit instruction - ES3 ES3 Output instruction PWM DPWM Range of pulse output width S1 0–30000 0–60000 Range of pulse output cycle S2 0–30000 0–60000 t T