Chapter 6 Applied Instructions 3. The output point for the pulse direction output device D 2 is affected by the scan cycle if it is not the recommended output point in the table above. 4. The pulse direction output device D 2 changes its own state according to the minus or plus sign in S . D 2 is OFF if S is plus (+) and D 2 is ON if S is minus (-). 5. There is no ramp-up or ramp-down setting in the instruction. The instruction does not perform a ramp-up operation at the beginning or ramp-down at stopping. If you want the ramp-up and ramp-down function, use the DRAMP instruction (API 0703) for increasing and decreasing the pulse output frequency. 6.
While the instruction is executing the pulse output, the output immediately stops if the drive condition changes to OFF. 7. When the direction outputs are not using the default outputs to output, you can refer to the table below for setting up the time for directional outputting goes first before pulse outputting. So that you can be sure the outputting only happens when switching to the direction outputs. The unit for SR is millisecond and the range is 0-20 ms. Default is 0, indicating inactive. Note: the time source here is from PLC scan time. 8. Refer to Example 3 from the DJOG instruction (API 2703) for programming in ST language. 6_ Example When M0 is ON, Y0 outputs the pulse at 20 kHz.
Y1 = OFF means the positive direction for the pulse output. 6-789 Output point for D1 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 SR number SR640 SR641 SR642 SR643 SR644 SR645 SR646 SR647