13 . Real Time Calendar Time Design Examples M11 When M11 = ON, RST M0 instruction will be executed for stopping the auxiliary motor and starting the main motor Clear the current running time of the auxiliary motor Reset M11 Program Description: z When X0 = OFF, Y0 and Y1 = OFF, both main / auxiliary motor will not run. z When X0 = ON, the running status of Y0 (main motor) and Y1 (aux. motor) will be decided by the ON/OFF status of M0 so as to control the two motors running in turns. z For main motor, D0 and D1 record the current time measured in hour and the current time that is less than an hour (0~3599s).
For auxiliary motor, D2 and D3 record the current time measured in hour and the current time that is less than an hour (0~3599s). z 16-bit instruction supports the set time up to 32,767 hours and 32-bit instruction supports the set time up to 2,147,483,647 hours. z The timer will go on timing after the set time is reached. For restart timing, users need to clear the current time stored in D0~D3 and reset flag M10 and M11. DVP-PLC Application Examples 13-7 RST M0 ZRST D2 D3 RST M11